× Close

HV Diagnostics HVA60: Hipot Tester

$0.00

The HV Diagnostics HVA60 Hipot Tester is a very popular, single piece instrument which is widely used on long 35/33kV cable systems found in electrical utilities, wind and solar farms, etc.

SKU: hv-diagnostics-hva60 Categories: , , , ,

More Information

The HVA60 VLF / DC high voltage test instrument is the instrument of choice when you require a single instrument that can test the full range of Medium Voltage cables available

This very popular, single piece instrument is widely used on long 35/33kV cable systems found in electrical utilities, wind and solar farms, etc. The HVA60’s portable design has a total weight equivalent to just one piece of many two piece VLF 60kV units available on the market. In addition, setting up the HVA60 instrument is simple with no cumbersome interconnects between various modules that make up a typical two-piece design.

Having both VLF AC and DC outputs, the HVA60 is not simply a high voltage instrument for testing MV cables, the unit can also be used for testing Vacuum bottles, cable jackets/sheaths, rotating machines, transformers, switchgear, etc. Test reports are downloaded to the instrument’s internal memory or to a USB flash drive.

As with all HVA units, fully automatic test sequences, digital RMS metering, and integrated storage of test results make the HVA60 a top seller.

Features:

  • Test your 35kV below MV cable systems.
  • Single Piece Design
  • Weighs only 126 lbs / 57kg
  • Perform tests fully automatically
  • Real time oscilloscope display
  • Insulation Resistance & Cap. measurement
  • RMS Metering of Current and Voltage
  • Output Frequency optimization
  • Internal Storage of Test Reports
  • Download to PC and / or USB flash drive
  • Unlimited duty cycle
  • Bright backlit LCD display
  • Power supply immunity and independence
  • Low maintenance, oil-free design
  • HVA Control Center – User friendly software for immediate, professional detailed reporting and setup

Output Modes

  • VLF 44kVrms / 62kVpk output
  • DC ±60kV
  • VLF Sinewave / Squarewave & DC outputs
  • Cable Jacket / Sheath testing
  • Vacuum bottle testing
  • Fault Conditioning / Fault Trip
  • Load independent output waveform

Safety

  • Remote interlock “kill switch” and HV status indication
  • Short circuit detection
  • Local Emergency off button
  • 12kV power frequency voltage feedback protection
  • Flashover voltage detection
  • Integrated internal discharge of DUT

Optional Accessories

TD60| PD60-2 | PD60-2/TD

Technical Specifications:

Ordering Information:

706 001

Power Supply/Input Voltage:

110 to 240V AC ±10% (50/60Hz)

Input Power Requirements:

1.2kVA

Rated Max Output Voltage:
Sinusoidal RMS/Peak
Squarewave
DC

44kV/62kV
60kV
±60kV

Rate Max Output Current:
Sinusoidal RMS
DC/Squarewave

26mA
40mA

Output Frequency (default 0.1Hz):

0.01Hz to 0.1Hz adjustable small increment of 0.01Hz (10 frequencies)

Frequency Optimization:

Yes

Maximum Output Load Capability @ maximum voltage and frequency:

1µF
*10 000ft
*3km

Maximum Output Load Capability @ Reduced Frequency and / or voltage:

5µF
*50 000ft
*15km

Metering:
Voltage
Current
Capacitance
Resistance
Timing
Fast Arc/Flashover
Waveform

0.1kV Resolution ±1% Accuracy
1 µA Resolution ±1% Accuracy
0.1 nF to 20 µF Range
0.1MΩ to 20GΩ Range
Included and integrated
Detection Included and Integrated
Real time oscilloscope display of actual output voltage waveform

Output Mode (all load independent & symmetrical):

VLF AC Sinewave
VLF AC Squarewave
DC (both Positive and Negative Polarity)
Fault Condition Mode / Fault Trip Mode
Vacuum Bottle Test Mode (DC) – optional
Cable Jacket / Sheath Test Mode

Output Duty:

Continuous

Computer Interface:

RS232 Standard, USB Flash Memory Download Module (optional)
HVA Contol Center Software included with every HVA instrument

Memory / Test Record Storage:
Built in Memory
USB Flash Drive

50 Test Records
Unlimited (see options)

No. of programmable Automatic Test Sequences:

40

Standard HV Test Lead Cable Included:

15ft/4.5m

Weight:

126 lbs/57kg

Dimensions:
Imperial (inches)
Metric (mm)

18 x 13.5 x 20.5
450x340x520

Environmental:
Storage
Operating
Humidity

-13°F to 158°F / -25°C to 70°C
23°F to 113°F / -5°C to +45°C
85% RH non-condensing


Documentation:

Equipment Brochure


Additional information

Manufacturer

UOM - Unit of Measure

Reviews

There are no reviews yet.

Be the first to review “HV Diagnostics HVA60: Hipot Tester”

Your email address will not be published. Required fields are marked *