Programma CSU-600AT
High Current Test Set
- Compact and rugged
- Quick and easy to use
- Broad application range
- Excellent weight/performance ratio
These high-current supply units have two main fields of application. The first is to conduct primary tests on protective relays. A primary test shows whether all parts of the protection system are functioning together properly within the specified time limits under operating conditions. The second field of application involves conducting current tests on low-voltage circuit breakers and overcurrent devices.
SPECIFICATIONS
Specifications are valid at nominal input voltage and an ambient temperature of +25°C, (77°F).
Environment
Application field The instrument is intended for use in high-voltage substations and industrial environments.
Temperature
Operating 0°C to +50°C (32°F to +122°F)
Storage & transport -40°C to +70°C (-40°F to +158°F)
Humidity 5% – 95% RH, non-condensing
General
Mains voltage 115 or 230 V AC, 50 / 60 Hz
Power consumption 115 V, 667 VA cont. (interm. 3738 VA)
(max) 230 V, 851 VA cont. (interm. 6440 VA)
Protection Thermal cut-outs and miniature circuit
breakers
Dimensions
Instrument 356 x 203 x 241 mm (14.0” x 8.0” x 9.5”)
Transport case 610 x 290 x 360 mm (24.0 x 11.4 x 14.2”)
Weight 21.9 kg (48 lbs) 38.3 kg (84.4 lbs) with
accessories and carrying case
Current cables 2 x 5 m (16 ft), 50 mm²
Measurement section
Output for external 600/6 A ammeter
Inaccuracy ±0.5%
Timer (only CSU600AT)
Range 0-999.999 s
Resolution 1 ms
Inaccuracy ±0.02% of shown value + 0 to 2 ms
Other Output for starting external timer
Outputs, AC, intermittent output 1) (CAT I)
|
115 V mains voltage |
230 V mains voltage |
||
Current |
Load time |
Minimum output voltage |
Load time |
Minimum output voltage |
0 A |
Cont. |
6.0 V |
Cont. |
9.5 V |
75 A |
– |
– |
Cont. |
9.3 V |
100 A |
Cont |
5.6 V |
1 h |
9.0 V |
200 A |
15 min |
5.3 V |
5 min |
8.5 V |
300 A |
1.5 min |
4.9 V |
2 min |
8.0 V |
400 A |
1 min |
4.6 V |
1 min |
7.5 V |
500 A |
20 s |
4.2 V |
30 s |
7.0 V |
600 A |
15 s |
3.9 V |
20 s |
6.5 V |
1) Maximum load time from cold state 25°C (77°F). Not valid for repeated tests.
Maximum cable lengths at 600 A
115 V mains 2 x 5 m (16 ft), 70 mm²
230 V mains 2 x 5 m (16 ft), 50 mm²
2 x 10 m (33 ft), 70 mm²
2 x 15 m (49 ft), 95 mm²
Documentation: